Notes
Slide Show
Outline
1
Indirect Cooling Using
Water Mist
  • Ariam C. Luers, Gerard G. Back, Scott A. Hill
  • Hughes Associates, Inc.
  • Baltimore, MD


  • Dr. Patricia Tatem, Dr. Frederick Williams
  • Naval Research Laboratory
  • Washington, DC


2
Indirect Cooling Using Water Mist
  • Background
  • Previous testing conducted to develop systems and technologies to help reduce the number of personnel required for Damage Control operations on a Navy ship.
  • Water mist used to provide boundary cooling for spaces surrounding the fire compartment.
  • Traditional means of boundary cooling was accomplished by spraying water on the bulkhead – using fire hoses and/or sprinklers.
3
Indirect Cooling Using Water Mist
  • Background
  • During the reduced manning tests, we learned that any water in the damaged space was beneficial to cooling the compartment.
  • Wanted to develop a system that could survive in the damaged compartment.
  • Concept of using sidewall nozzles introduced.
4
Indirect Cooling Using Water Mist
5
Indirect Cooling Using Water Mist
6
Indirect Cooling Using Water Mist
  • Water Mist Attributes


  • Thermal Management
  • Reduced Vent Flow
  • Oxygen dilution by water vapor and vitiated gases.


7
Indirect Cooling Using Water Mist
  • Test Objectives


  • Scoping tests to conducted to evaluate the ability of low pressure and high pressure water mist systems to:
  • Thermally manage the compartments directly damaged by the weapons hit.
  • Prevent fire spread to adjacent spaces.



8
Indirect Cooling Using Water Mist
  • Measures of Performance


  • Thermal management
    • Limit fire spread (i.e., compartment temps < 250°C)
    • Prevent flashover (i.e., compartment temps < 500°C)
  • Fire extinguishment
  • Localized heating effects
  • Energy absorbed by water mist system
9
Indirect Cooling Using Water Mist
10
Indirect Cooling Using Water Mist
  • Vent Openings
11
Indirect Cooling Using Water Mist
12
Indirect Cooling Using Water Mist
  • 0.6 MW
  • 1.2 MW
  • 2.0 MW
  • 4.0 MW
  • Multiple Fires


13
Indirect Cooling Using Water Mist
  • Test Variables


  • Pan Location (Forward, Aft)
  • Proximity Effects
  • Vent Openings (5 Outboard, 2 Inboard)
  • Obstructions


14
Indirect Cooling Using Water Mist
  • Test Results


  • Over 70 tests conducted.
  • Baseline tests (i.e., no mist) conducted for the fire scenarios.
  • Nozzle performance compared against baseline to evaluate systems.


15
Indirect Cooling Using Water Mist
  • Test Results – Summary of System Performance
16
Indirect Cooling Using Water Mist
17
Indirect Cooling Using Water Mist
  • Test Results – Thermal Management


  • 0.6 MW Fires – Upper layer temps did not exceed fire spread criteria 250°C.
  • 1.2 MW Fires – Upper layer temps above 250°C.  Fire spread criteria exceeded during some high pressure tests and all of the low pressure tests.
18
Indirect Cooling Using Water Mist
  • Test Results – Thermal Management


  • 2.0 MW Fires – Baseline exceeded 250°C.  High pressure – 17 of 24 met goal; Low pressure – none met goal.
  • 4.0 MW Fires – Baseline exceeded 500°C.  Flashover prevention was achieved during all tests.  Fire spread criteria exceeded for all tests.


19
Indirect Cooling Using Water Mist
  • Test Results – Fire Extinguishment
  • Larger fires easier to extinguish than smaller fires.



20
Indirect Cooling Using Water Mist
  • Summary/Conclusions


  • Overall high pressure better than low pressure – in terms of fires extinguished and thermal management.
  • Example - 2.0 MW fire scenario – average overhead temperatures exceeded fire spread criteria during all of low pressure tests (100%) and less than half of high pressure tests (30%).
21
Indirect Cooling Using Water Mist
  • Summary/Conclusions


  • For systems with equivalent flow rates, high pressure performed better than low pressure.
22
Indirect Cooling Using Water Mist
  • Summary/Conclusions


  • For systems with equivalent flow rates, high pressure performed better than low pressure.
23
Indirect Cooling Using Water Mist
  • Summary/Conclusions


  • Nozzle design (pattern, flow, projection) has an impact on thermal management – flow rate alone is not an indicator of performance.



24
Indirect Cooling Using Water Mist
  • Summary/Conclusions


  • Overall, both high pressure and low pressure water mist systems were shown to be effective in terms of thermal management.
  • It is important to note that none of the water mist systems were optimized.


25
Indirect Cooling Using Water Mist
  • Summary/Conclusions
  • Additional testing is currently being conducted to further evaluate low, medium and high pressure water mist systems.
  • These tests will evaluate different types of fires (i.e., Class A and Class B), various types of nozzles, and different nozzle spacings.